Typical part load efficiencies, Chillers turbochill™ air cooled and freecool, Desi gn – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 38

Advertising
background image

38

Chiller Technical Manual 7525355 V1.1.0_03_2013

D

esi

gn

Chillers

TurboChill™ Air Cooled and FreeCool

Typical Part Load Efficiencies

The following graph gives a general indication of the effect of reduced load on the performance of the unit, for

performance details, please contact Airedale.

ESEER Calculations

The quoted EER figures cover the performance of the unit ONLY at the standard rating conditions of 7/12°C water,

35°C ambient. The ESEER (European Seasonal Energy Efficiency Ratio) calculation method has been developed by

Eurovent to give a single value that is a realistic indication of the efficiency of the chiller across the year round range of

operation.

The ESEER value is calculated from the unit’s performance at 20, 25, 30 and 35°C ambient temperatures for 25, 50,

75 and 100% loading stages respectively, and with a fixed 7°C supply temperature. All calculations assume the system

operates with 100% water.

ESEER = A●EER

100%

+ B●EER

75%

+ C●EER

50%

+ D●EER

25%

A, B, C and D are weighting factors 0.03, 0.33, 0.41 and 0.23.

A

B

C

D

Temperature

35°C

30°C

25°C

20°C

Capacity Requirement

100%

75%

50%

25%

Percentage of Total Hours

0.03

0.33

0.41

0.23

%

o

f F

ul

l L

oa

d

EE

R

, C

oo

lin

g

C

ap

ac

ity

a

nd

In

pu

t

250%

1

2
3

200%

150%

100%

50%

0% 25%

@ 20°C

Ambient

50%

@ 25°C

Ambient

75%

@ 30°C

Ambient

100%

@ 35°C

Ambient

% of Full Load Capacity

Key:

1 = EER

2 = Output kW

3 = Input kW

SEER

The quoted EER figures cover the performance of the unit ONLY at the standard rating conditions of 7/12°C water, 35°C

ambient. The SEER calculation method is used for part of the Building Regulations Part “L” to give a single value that

realisticly indicates the efficiency of the chiller across the year round range of operation.

The SEER value is calculated from the unit’s performance at 20, 25, 30 and 35°C ambient temperatures for all loading

stages, and with a fixed 7°C supply temperature. All calculations assume the system operates with 100% water.

SEER = A●EER

100%

+ B●EER

75%

+ C●EER

50%

+

D●EER

25%

Where A,B,C and D are specific weighting factors 0.12, 0.32, 0.36 and 0.2 for use on calculating SEER.

A

B

C

D

Temperature

35°C

30°C

25°C

20°C

Capacity Requirement

100%

75%

50%

25%

Percentage of Total Hours

0.12

0.32

0.36

0.2