Installation Data

Water Systems and Recommended Flow Schemes

The recommended requirements to allow commissioning to be carried out correctly are:

The inclusion of Binder Points adjacent to the flow and return connections, to allow temperature and pressure

readings

A flow switch or equivalent, fitted adjacent to the water outlet side of the Chiller

A 1/16” mesh strainer fitted prior to the evaporator inlet

A water-flow commissioning valve set fitted to the system

In multiple chiller installations, 1 commissioning valve set is required per chiller

Air vents are to be installed at all high points and where air is likely to be trapped at intermediate points

Drain points are to be installed at all low points in the system and in particular adjacent to the unit for

maintenance to be carried out. The unit must be drained for winter shutdown.

Isolating valves should be installed adjacent to all major items of equipment for ease of maintenance

Balancing valves can be installed if required to aid correct system balancing

All chilled water pipe work must be insulated and vapour sealed to avoid condensation

If several units are installed in parallel adjacent to each other, reverse return should be applied to avoid

unnecessary balancing valves

Pump Statement

When installing circulating water pumps or equipment

containing them, the following rules should be applied:

Ensure the system is filled with water then vented and the pump primed with water before running the pump,

this is required because the pumped liquid cools the pump bearings and mechanical seal faces

To avoid cavitation the NPSH (Net Positive Suction Head) incorporating a safety margin of 0.5m head must be

available at the pump inlet during operation

Interlocks & Protection

Always electrically interlock the operation of the chiller with the pump controls

and water flow switch.

These safety devices prevent the chiller operating with low water flow which can cause serious damage.

CAUTION

Failure to install both safety devices will invalidate the chiller warranty.

Do not rely solely on the BMS to protect the chiller against low flow conditions.

An evaporator pump interlock and flow switch MUST be directly wired to the Chiller, refer to

Interconnecting Wiring

.

Flow Schemes

Basic Supplied Water Schematic - Evaporator only

(Includes Flow Proving Device)

PDZAL

DRAIN ONLY PRESENT

ON 4 PASS

EVAPORATORS

2 AIR VENTS PRESENT

ON

4 PASS EVAPORATORS

2

5

5

11

3

3

2

SUPPLY WATER

RETURN WATER