Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Operation in advanced display mod

9.6.11

ACTUAL CONFIG (actual slave configuration)

Main menu || DIAGNOSE || ACTUAL CONFIG ||

This function displays the status of the actual configuration of the individual AS-i
slaves.

A help appears at the end of the list explaining the abbreviations:

After selecting the desired AS-i slave address, the values for the current configu-
ration data are displayed after the respective address in the following order:

IO (I/O-Configuration) ID (ID-Configuration) xID1 (extended ID1) xID2 (extended
ID2).

ACTUAL CONFIG
0A | 1A-C
....
30A-X | 31A-D
| 1B-X
....
30A | 31B-F
HELP:
X O.K.
D DETECTED ONLY
UNKNOWN SLAVE
P PROJ. ONLY
MISSING SLAVE
C TYPE CONFLICT
F PERIPH. FAULT
A DUPLICATE ADDR

X (O.K.): The configuration data for the detected AS-i slave agree with

the designed in configuration data.

D (Detected Only): An AS-i slave is detected at this address, but it was not

designed in.

P (Projected Only): An AS-i slave was designed in at this address, but it was not

detected.

C (Type Conflict): The configuration data for the detected AS-i slave do not

agree with the designed in configuration data. The actual exist-
ing configuration of the connected AS-i slave is displayed.

F (Periph. Fault): The AS-i slave has a peripheral error.

A (Duplicate Adr.): Two AS-i slaves at the indicated address.