EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual

Page 166

Advertising
background image

166

Subject to reasonable modifications due to technical advances

Id.-No.: 103329

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Appendix: Example for startup on a Siemens S7

If this bit is set, the AS-i Master immediately switches to the offline phase and
stops AS-i communication when an AS-i configuration error is detected. This re-
sults in the connected AS-i output modules immediately switching to safe mode
(outputs turned off).

AS-i Configuration Mode

Bit 6: 0 = no action, 1 = turn on configuration mode of AS-i Master

Setting Bit 6 switches the AS-i Master to configuration mode. Then for example
the command interface can be used to save an existing AS-i configuration using
the controller.

The rising edge is used for switching. After Bit 7 = 1 in the input flags has indicat-
ed that the AS-i Master is in configuration mode, output bit 6 must be reset again
by the controller.

AS-i Protected Mode

Bit 6: 0 = no action, 1= turn on protected mode of AS-i Master

After successful configuration of the AS-i Master through the command interface,
the AS-i Master can be switched back to protected mode.

The rising edge is used for switching. After Bit 7 = 0 in the input flags has indicat-
ed that the AS-i Master is in configuration mode, output bit 7 must be reset again
by the controller.

The table shows an AS-i circuit which is in operation. Since there is no AS-i error,
bits 4 - 7 in the input byte are ZERO.

In the case of AS-i Slave address 1, this is a 4 I/O module. In this module
Output 3 is set and Input 1 allocated.

Advertising