Coupling slave – EUCHNER AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor for 2 AS-i circuits User Manual

Page 75

Advertising
background image

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Operation in advanced display mod

Subject to reasonable modifications due to technical advances

Id.-No.: 103329

Issue date - 24.10.2008

EUCHNER GmbH + Co. KG

75

Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen

Tel. +49/711/75 97-0 • Fax. +49/711/753316

The following error messages are possible:

Press the OK key to save the learned code table or press ESC to discard it.

9.5.1.3

COUPLING SLAVE

Main Menu || AS-I SAFETY || TEACH CODES || COUPLING SLAVE ||

This menu point allows you to teach the code table for a coupling slave. To con-
tinue, enter the PIN and confirm with OK.

In the following menu you select the AS-i circuit.

After selecting the AS-i circuit the safe unit switches to configuration mode.

Then enter the slave address.

The teach procedure was successful if after approx. 2 s an OK appears in the dis-
play.

Save with OK, or cancel the process by pressing ESC.

Message Description

RR

Both contacts open

RX

Left contact open, right contact closed.

XR

Right contact open, left contact closed.

TEACH CODES
ENTER PIN
0000
OK

AS-I CIRCUIT 1
AS-i CIRCUIT 2

COUPLING SLAVE
SLAVE ADDR.

––1

ESC

COUPLING SLAVE
SLAVE ADDR.

––1

ESC

[OK]