AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Spezifications

4.2

Consideration of failure probability according to IEC 61 508

To allow calculation of failure probability for the entire system, the AS-i Safety
Monitor returns a component which depends on the maximum uninterrupted
switch-on time of the output circuit(s).

This results in the following table:

The switch-on time describes the period of time until the safety function was re-
quested, or the maximum period of time between two executed safety checks.
During this check, safe shutdown is tested by actuating every safe sensor.

The total operating time describes the safety system's service life from commis-
sioning to disassembly; it is used as the basis for calculating the failure probabili-
ty.

Together with the failure probabilities of the other components used in the safety
system (e.g. AS-i slaves) it is then possible to determine the overall failure proba-
bility. The resulting value can be used for categorising the safety system under
the respective safety level in accordance with IEC 61 508.

4.3

Scope of delivery

The basic unit consists of:

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor.

The following accessories are available:

Cage spring terminals ZMO-ZB-KK8-M

Screw terminal ZMO-ZB-AK-8

Cable for programming with PC ZMO-ZB-PGK

1 chip card ZMO-ZB-M11

10 chip cards ZMO-ZB-M10

Configuration software ZMO-ZB-ANWPG ASIMON 3 G2

Failure probability on request depending on switch-on time

Switch-on time

Total operating time

PFD

12 months

10 years

<

9,25 x 10

-6

Probability of failure per hour

Switch-on time

Total operating time

PFH

12 months

10 years

< 5,36 x 10

-9