AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor

Appendix: Example for startup on a Siemens S7

In the structure of the 16 byte I/O data field each AS-i slave has a 4-bit data field.
This is determined by the address of the AS-i slave within the AS-i circuit.

The data for the slaves present and projected in the AS-i circuit are refreshed
based on their position in the I/O data field.

The data fields for non-present slaves are filled with zero.

This means for example the AS-i data for the AS-i slave having Address 12 occu-
py bits 7 - 4 in I/O byte 8 of the controller.

Assignment of the I/O address and AS-i slave address

Address byte

Bits 7 - 4

Bits 3 - 0

I/O byte 2

flags

slave 1

I/O byte 3

slave 2

slave 3

I/O byte 4

slave 4

slave 5

I/O byte 5

slave 6

slave 7

I/O byte 6

slave 8

slave 9

I/O byte 7

slave 10

slave 11

I/O byte 8

slave 12

slave 13

I/O byte 9

slave 14

slave 15

I/O byte 10

slave 16

slave 17

I/O byte 11

slave 18

slave 19

I/O byte 12

slave 20

slave 21

I/O byte 13

slave 22

slave 23

I/O byte 14

slave 24

slave 25

I/O byte 15

slave 26

slave 27

I/O byte 16

slave 28

slave 29

I/O byte 17

slave 30

slave 31