Digital frequency extension module | Parameter setting & configuration

Parameter reference

Parameter list | C13036

C13036

C13037

C13040

C13041

Parameter | Name:

C13036 | Actual position DFIN

Data type: INTEGER_32

Index: 11539

d

= 2D13

h

Display range

(min. value | unit | max. value)

-214748.3647

Unit

214748.3647

;

Read access … Write access … CINH … PLC-STOP … No transfer

Scaling factor: 10000

Parameter | Name:

C13037 | Actual speed DFIN

Data type: INTEGER_32

Index: 11538

d

= 2D12

h

Display range

(min. value | unit | max. value)

-214748.3647

Unit/s

214748.3647

;

Read access … Write access … CINH … PLC-STOP … No transfer

Scaling factor: 10000

Parameter | Name:

C13040 | Resp. to track monitoring DFIN

Data type: UNSIGNED_8

Index: 11535

d

= 2D0F

h

Digital frequency extension module in module receptacle MXI1:

Response when track monitoring is triggered for digital frequency input X9

• Track monitoring is triggered if a signal cable (A, B, or Z) is interrupted.
Selection list

(Lenze setting in bold)

1 Fault
2 Trouble
3 Quick stop by trouble
5 Warning
4 Warning locked
6 Information
0 No response

;

Read access ; Write access … CINH … PLC-STOP … No transfer

Parameter | Name:

C13041 | Resp. to DFIN enable sig. miss.

Data type: UNSIGNED_8

Index: 11534

d

= 2D0E

h

Digital frequency extension module in module receptacle MXI1:

Response when "Enable" signal at digital frequency input X9 fails
Selection list

(Lenze setting in bold)

1 Fault
2 Trouble
3 Quick stop by trouble
5 Warning
4 Warning locked
6 Information
0 No response

;

Read access ; Write access … CINH … PLC-STOP … No transfer