C14042 | resp. to vcc error dfin, C14050 | signal source dfout, C14051 | no. of increments dfout – Lenze E94AYFLF Digital frequency module User Manual

Page 42: C14052 | zero pulse offset dfout, C14042, C14050, C14051, C14052, Is wit

Advertising
background image

Digital frequency extension module | Parameter setting & configuration

Parameter reference

Parameter list | C14042

42

L

EDS94AYFLF EN 3.2 - 10/2010

C14042

C14050

C14051

C14052

Parameter | Name:

C14042 | Resp. to Vcc error DFIN

Data type: UNSIGNED_8

Index: 10533

d

= 2925

h

Digital frequency extension module in module receptacle MXI2:

Response when monitoring for encoder voltage supply at digital frequency input X9 is triggered

• Monitoring is triggered if the encoder voltage controlled by the digital frequency input reaches the voltage limit.
Selection list

(Lenze setting in bold)

1 Fault
2 Trouble
3 Quick stop by trouble
5 Warning
4 Warning locked
6 Information
0 No response

;

Read access ; Write access … CINH … PLC-STOP … No transfer

Parameter | Name:

C14050 | Signal source DFOUT

Data type: UNSIGNED_8

Index: 10525

d

= 291D

h

Digital frequency extension module in module receptacle MXI2:

Selection of the signal source for digital frequency output X10
Selection list

(Lenze setting in bold)

1 None
2 Digital frequency input DFIN
3 Motor feedback system
4 Load feedback system
5 Resolver
6 Encoder
7 Application [Incr./ms]

;

Read access ; Write access … CINH … PLC-STOP … No transfer

Parameter | Name:

C14051 | No. of increments DFOUT

Data type: UNSIGNED_32

Index: 10524

d

= 291C

h

Digital frequency extension module in module receptacle MXI2:

Number of increments for digital frequency output X10

• Definition of the number of pulses for one "mechanical" revolution.
Setting range

(min. value | unit | max. value)

Lenze setting

1

16384 2048

;

Read access ; Write access … CINH … PLC-STOP … No transfer

Parameter | Name:

C14052 | Zero pulse offset DFOUT

Data type: UNSIGNED_16

Index: 10523

d

= 291B

h

Digital frequency extension module in module receptacle MXI2:

Zero pulse offset for digital frequency output X10

• Offset for displacing the zero pulse to be output.
Setting range

(min. value | unit | max. value)

Lenze setting

0

Incr.

65535 0 increments

;

Read access ; Write access ; CINH … PLC-STOP … No transfer