5. how to wire, Recommended cables, Caution – RKI Instruments RM-5000 Series Indicator/Alarm Unit User Manual

Page 21

Advertising
background image

4 How to Use

4-5. How to wire

- 21 -

RM-5000

4-5. How to wire














<Recommended Cables>

Model Cable

specifications

GP-5001
NC-5001
NC-5001W
SP-5001

Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVV (1.25 sq or 2.0 sq) - 4-core or 6-core
Signal:

Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core

Contact:

Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core

NP-5001

Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 4-core or 6-core
Signal:

Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core

Contact:

Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core

OX-5001
OX-5002
RM-5002

Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Signal:

Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core

Contact:

Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core

GH-5001

Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 3-core or 5-core
Signal:

Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core

Contact:

Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core

EC-5002

Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core or 4-core
Signal:

Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core

Contact:

Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core

RM-5003

Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 3-core
Signal:

Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core

Contact:

Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core


CAUTION

• Use the specified cables for each of the connections between the indicator/alarm unit and the

detector head.

• When wiring, be careful not to apply stresses on the terminal plate when (overweight) cables are

installed.

• The power cables and signal cables must not be installed together with the motor power cables,

etc.

• When stranded wires are used, prevent wires from contacting each other.
• Use the specified tools to wire.