7 Maintenance

7-2. Regular maintenance mode

- 55 -

RM-5000

<<Regular Maintenance Mode>>

During maintenance
During inhibit

Lamp on
Lamp off
Lamp blinking

User Mode

In "1-8.M MODE", press the
SET key.

Then press the SET key
again for three seconds.

Regular Maintenance Mode

2-0. GAS TEST

Perform a test with the gas.
Similar to the detection
mode, the reading changes
and the alarm lamp lights up
after the gas is introduced,
but the contact is not
activated.

(Alternate Display)

2-1. ZERO

Perform the zero adjustment.

Zero Adjustment

=> P69

2-2. SPAN

Perform the span
adjustment.

Span Adjustment

=> P70

2-3. LAST CAL

Show the last calibrated date.
(Example: 2011/01/01 12:00)

2-4. HEAT CUR

Display the value of a current
that runs in the heater of the
sensor.
(GP-5001, NC-5001,
NC-5001W, GH-5001 only)

2-5. SETTING1

Specify the environmental
setting 1.

Environmental Setting 1

=> P57