RKI Instruments RM-5000 Series Indicator/Alarm Unit User Manual

Page 49

Advertising
background image

6 Operations and Functions

6-3. External output operation

- 49 -

RM-5000

<NC-5001W>














NOTE

NC-5001W offers two reading ranges (low and high ranges).
If the displayed combustible gas concentration rises above the full scale of the low range, the display is
automatically switched to the high range.
On the other hand, if the gas concentration drops below the full scale of the low range, the display is
automatically switched back to the low range.
The low range is indicated by lighting of the WL display, and the high range by lighting of the WH display,
informing the present reading range (low or high range).

Example
Target gas

:

Isobutane

Reading range

:

0-2000 ppm

/

0 - 100%LEL

Status display

:

WL (low range)

/

WH (high range)



2.5 mA

4 mA

20 mA

22 mA

Full scale

Gas concentration

External output

0

Zero

suppression

Detection mode

Maintenance mode

16 mA

High range

Low

range