Alarm setpoint value setting 1 "2-5" - "set 1, Fault alarm test "2-5" - "set 3, Warning – RKI Instruments RM-5000 Series Indicator/Alarm Unit User Manual

Page 58

Advertising
background image

7 Maintenance

7-2. Regular maintenance mode

RM-5000

- 58 -

<Alarm Setpoint Value Setting 1 "2-5" - "SET 1">

<<Alarm Setpoint Value Setting>>


<Fault Alarm Test "2-5" - "SET 3">








During maintenance
During inhibit

Lamp on
Lamp off
Lamp blinking

SE 1. ALM P

Press SET key.

Return to SET 1.ALM P

First Alarm Setpoint Value
Setting

Press the ▲ or ▼ key to change
the value, and then press the
SET key to confirm the value.

Second Alarm Setpoint Value
Setting

Press the ▲ or ▼ key to change
the value, and then press the
SET key to confirm the value.

During maintenance
During inhibit

Lamp on
Lamp off
Lamp blinking

SE 3.F TEST

Press SET key.

Fault Test ON/OFF

Select either ON/OFF.
Press the ▲ or ▼ key to select ON in
the display, and then press the SET
key to activate the fault alarm.
Select OFF in the display and press
the SET key to deactivate this
menu.(Alternatively, press the MODE
key to deactivate this menu.)

WARNING

Because the contact (fault) can be activated only by a fault alarm test in the maintenance mode, be
careful to perform the test. The fault alarm test cannot be performed during inhibit ( I ).