Recommended Torque
Values
When reinstalling components, or when reassembling the cabinet, tighten the
following bolt sizes to the specified torque values:
Table 1 - Torque Values for Hardware
1/4 in. hardware
8 N•m (6 lb•ft)
5/16 in. hardware
15 N•m (12 lb•ft)
3/8 in. hardware
27 N•m (20 lb•ft)
1/2 in. hardware
65 N•m (48 lb•ft)