3. To adjust the distance from the blades to the bar, disconnect the threaded

connecting rod at the handle operating lever.

4. Turn the threaded connecting rod to lengthen or shorten it. This will

adjust the position of the isolation switch blades in the ON and OFF
position.

Auxiliary Contacts Inspection
and Replacement

1. Complete the Power Lockout Procedure (refer to

Power Lock-out

Procedure on page 41

).

2. Inspect the auxiliary contacts for wear, scorching or heat damage. Replace

any damaged contacts. The contacts have a mean time between failure
(MTBF) rating of 20 million operations if used within the operating
specifications.

3. To remove the contact, turn both of the D-head fasteners until the flat

sections are aligned with the edge of the contact (See

Figure 59

).

4. Remove the contact from the housing.

5. Disconnect the wires from the auxiliary contact.

6. Reverse the procedure to replace the auxiliary contact.

7. Ensure the contact is correctly positioned into the contact carrier (see

Figure 59

).

Figure 59 - Auxiliary Contact Orientation

ATTENTION: To avoid shock hazard, lock out incoming power (refer to

Power

Lock-out Procedure on page 41

) before working on the equipment. Verify with a

hot stick or appropriate voltage measuring device that all circuits are voltage
free. Failure to do so may result in severe burns, injury or death.

CATALOG NO.

700-CPM

SER. A

20

AMP

CATA

LOG NO.

700-CPM

SER. A

20

AMP

CATALOG NO.

700-CPM

SER. A

20

AMP

CATALOG NO.

700-CPM

SER. A

20

AMP

CATA

LOG NO.

700-CPM

SER. A

20

AMP

CATA

LOG NO.

700-CPM

SER. A

20

AMP

D-head Fastener

Correct

Incorrect

Advertising