Step 4 – closing the front of the plenum sections, Step 5 – extension and elbow assembly – Rockwell Automation 1512A MV Controllers, 400A One-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 87

Advertising
background image

Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

79

ArcShield Plenum Installation Instructions

Appendix B

The “End Cover Plate” must be mounted on the closed end of the Line-up at this
time during the assembly using 5/16 in. hardware (see

Figure 77

Left side).

STEP 4 – Closing the Front of
the Plenum Sections

After the first stage of the Plenum assemblies have been mounted, the Plenums
can then be “closed-up” by replacing the front duct sections as shown in

Figure 78

.

Figure 78 - Plenum Sections

STEP 5 – Extension and Elbow
Assembly

The 36" Extension components and 90° Elbow Section are to be attached using
5/16-in. hardware in the following sequence:

Step 5A – See

Figure 79

Step 5B – See

Figure 80

Step 5C – See

Figure 81

Top Plate

Bottom Plate

Front Closing P

late

IMPORTANT

Do not re-install the front duct section of the last Plenum on the exhaust side
of the Line-up at this time (refer to

STEP 6 – Mounting Extension/Elbow to

Plenum “Line-up” on page 80

for more information).

TIP

Use silicone caulking generously to fill any air gaps once the Plenum has been
securely mounted in place.

TIP

The Screen Cover Plate is attached in

Figure 80

.

Advertising