Cabinet preparation – Rockwell Automation 1512A MV Controllers, 400A One-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 93

Advertising
background image

Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

85

ArcShield Chimney Installation Instructions

Appendix C

Cabinet Preparation

In preparation for mounting a chimney, remove 1/4-20 fasteners from the Relief
vent on the top of the MV enclosure. Leave the four corner fasteners in place (see

Figure 87

).

The chimneys are designed to fit over the fastener heads at the (4) corners of the
Relief vent. The corner fasteners are required to secure the Relief vent during
installation.

Figure 86 - Relief Vent Fasteners (top view)

Figure 87 - Relief Vent

Relief vent

Relief fasteners

Corner fasteners