Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

43

Maintenance

Chapter 5

Figure 42 - Inspecting Isolation Switch in Open Position

6. Check the line and load sides of the contactor with a hot stick or

appropriate voltage measuring device to verify that they are voltage free
(see

Figure 43

).

a. Check for line-side voltage at the top vacuum bottle terminals.
b. Check for load-side voltage at the bottom vacuum bottle terminals.

See Detail A

Grounding Bar

Isolation Switch Blades

must fully engage

Grounding Pins of

Grounding bar

(Verify for each phase)

Isolation Switch Shutters

must be closed

(Verify for each phase)

Detail A

Grounding Pins

Isolation Switch

Blades in open

position

Viewed from back with components
removed for clarification