To reduce the gap distance – Rockwell Automation 1512A MV Controllers, 400A One-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 58

Advertising
background image

50

Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

Chapter 5

Maintenance

1. Complete the Power Lockout Procedure (refer to

Power Lock-out

Procedure on page 41

).

2. Open the medium voltage door. Use the Door Interlock Circumvention

procedure (refer to

Door Interlock Circumvention on page 40

) to move

the isolation switch handle halfway between the OFF and ON position
(see

Figure 49

). Keep the handle in this position until the adjustment

procedure is completed.

3. With the contactor in the OFF position, insert a 1.5 mm (0.060 in.) feeler

gauge in the gap between the interlock lever and the isolation switch
operating lever. The gap must be between 1.0 mm to 2.0 mm (0.039 in. to
0.078 in.).

4. To reduce the gap distance, follow steps 5-7.

To increase the gap distance, follow steps 8-10.

Figure 49 - Isolation Switch Handle Adjustments

To Reduce the Gap Distance

5. Loosen the two screws in the stop bracket and move the stop bracket up

against the interlock lever.

Isolation Switch
Operating Lever

Isolation Switch

Handle at halfway

position

Nyloc Nut

Contactor Interlock Lever

Contactor Interlock Rod

Stop Bracket

Switch Interlock Lever

Gap: 0.045...0.060 in.

(1.1...1.5 mm)