Installation – Arc-Resistant (ArcShield)

Chapter 3

Figure 23 - Access to Power Bus from Side and Rear of Cabinet

Side Access

A side bus access cover is located on each side of the controller, when required.

1. Remove the hardware from the appropriate side bus access cover.

2. Remove the side bus access cover (

Figure 23

).

3. ArcShield units at the end of a line-up have a ground connection to the

inner plate of the side bus access cover (see

Figure 25

and

Figure 26

). This

connection must be maintained to ensure unit arc resistant performance.