Ground bus, Incoming line cable connections – Rockwell Automation 1512A MV Controllers, 400A One-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 39

Advertising
background image

Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

31

Common Installation

Chapter 4

Ground Bus

1. See

Figure 36

to determine the correct ground splice configuration and

assemble as shown.

2. Torque the hardware to 15 N•m ± 1 N•m (12 lb•ft ± 1 lb•ft).

3. Check all hardware for correct tightness and replace all covers and plates.

Figure 36 - Typical Ground Bus Splicing Configuration (Front View)

Incoming Line Cable
Connections

Incoming cables are connected to the power bus in the last section on the left.

1. Remove the center-back plate or side plate to access the power bus. If access

to the rear of the unit is not possible, refer to

Access to the Power Bus on

page 7

for Standard or

Access to the Power Bus on page 20 of Chapter 3

for ArcShield enclosures.

Ground Bus Support

Main

Ground

Bus

Hex Nut

Lock Washer

Flat Washer

Ground Bus Splice Bar

ATTENTION: Ensure all barriers are replaced before re-energizing the
equipment. Failure to do so may result in electrical faults and cause damage to
equipment or severe injury to personnel.

ATTENTION: To avoid shock hazards, lock out incoming power (refer to

Power

Lock-out Procedure on page 41 of Chapter 5

) before working on the equipment.

Verify with a hot stick or appropriate voltage measuring device that all circuits
are voltage free. Failure to do so may result in severe burns, injury or death.

IMPORTANT

For Non-ArcShield units, cable size should not exceed 1-750 MCM or
2-500 MCM per phase.

For ArcShield units, cable size should not exceed 1-500 MCM or 2-4/0 per
phase. For larger cables, an incoming line module must be used.