Chapter 3

Installation – Arc-Resistant (ArcShield)

Opening the Medium Voltage Door

Figure 18 - Access to Medium Voltage Compartments

A Medium Voltage door is shown in

Figure 17

.

1. Electrically open the contactor by pressing the STOP button on the starter

or at the remote control location.

2. Move the isolation switch handle to the OFF position.

3. Unbolt the door locking bolts for the medium voltage door.

4. Turn the black release handle counter clockwise 90 º (

Figure 19

).

5. The door is now released and will swing open (the door is heavy and does

take some force to swing open).

6. Reverse the procedure to close the door. This sequence must be followed.

Door lock bolts must be adequately tightened (refer to

Recommended

Torque Values on page 2 of Chapter 1

).

ATTENTION: Complete the Power Lockout procedure (refer to

Power Lock-out

Procedure on page 41 of Chapter 5

) before beginning any service procedures to

the unit. Failure to do so may result in severe burns, injury or death.

IMPORTANT

The medium voltage door has its own isolation switch handle and interlocking
safeguards. The low voltage panel compartment and power cell are separated
by an isolation barrier.

IMPORTANT

Failure to follow the MV door opening procedure could damage or jam the
mechanical door interlocks. This could result in the mechanical interlocks not
operating as intended and could result in the door becoming jammed in the
closed position.

TIP

On all ArcShield starters, the sticker in

Figure 19

is attached to each

door for your reference.