48
Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013
Chapter 5
Maintenance
5. Use a 9/16 in. socket wrench to disconnect the power cables and bus bars
from the rear of the contactor.
Figure 47 - Removing the Contactor
6. Remove the nylon contactor bushing retaining screw from the contactor
operating lever.
7. Slide the contactor interlock rod and the nylon contactor bushing out of
the groove in the contactor operating lever (see
).
Contactor
Operating Level
Contactor
Interlock Rod