Access to the power bus, Rear access – Rockwell Automation 1512A MV Controllers, 400A One-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 28

Advertising
background image

20

Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

Chapter 3

Installation – Arc-Resistant (ArcShield)

Figure 22 - Joining Sections

Access to the Power Bus

Rear Access

1. Remove the hardware securing the center rear bus access cover (

Figure 23

).

2. Remove the center rear bus access cover.

3. Once the center rear bus cover is removed you will see the three bus bars

(

Figure 25

).

Power Bus

cutout holes

must align

Silicone is applied around

power bus cutout area to

prevent gas leakage

between joined cabinets

ATTENTION: This procedure requires contact with medium voltage
components. To avoid shock hazards, lock out incoming power before working
on the equipment (refer to

Power Lock-out Procedure on page 41 of Chapter 5

).

Verify with a hot stick or appropriate voltage measuring device that all circuits
are voltage free. Failure to do so may result in severe burns, injury or death.

ATTENTION: The rear cover plates are made from 12 gauge metal and
are mounted in board of the main structure. The covers will drop inside
if care is not taken as you remove the mounting bolts.