Rockwell Automation 1512A MV Controllers, 400A One-High Cabinet, Standard and Arc-Resistant Enclosure User Manual

Page 71

Advertising
background image

Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013

63

Maintenance

Chapter 5

If it is not possible to move the isolation switch handle to the OFF
position for reassembly, follow steps 11-13.

Installing Z-clip with Isolation Switch Handle in the OFF Position

5. Reattach the Z-clip using the self-tapping screws, but do not completely

tighten them.

6. Move the isolation switch handle to the OFF position.

7. Swing the door closed and inspect the position of the Z-clip with respect

to the handle pin.

8. Set the Z-clip so that it is just above the handle pin. Do not set the Z-clip

more than 3 mm (0.125 in.) above the pin. Open the door and tighten the
screws.

9. Close the door and move the handle to the ON position. Verify that the

handle pin overlaps the Z-clip and prevents the door from opening.

10. Move the handle to the OFF position and tighten the door locking bolts.

Installing Z-clip with Isolation Switch Handle in the ON Position

11. Close the door and tighten the door locking bolts.

12. Position the Z-clip as shown in

Figure 63

. Ensure the handle pin overlaps

the top portion of the Z-clip.

13. Use the self-tapping screws to reattach the Z-clip.

14. Complete steps 5-10 at the earliest opportunity to confirm that the Z-clip

assembly is correctly installed.

ATTENTION: The Z-clip assembly must be reassembled to ensure the
interlocking mechanism functions properly. Failure to do so will let
personnel access live medium voltage parts and may cause severe
burns, injury or death.