Setting the ip address by using dhcp/bootp – Rockwell Automation 1788-EN2DN Ethernet-to-DeviceNet Linking Device User Manual

Page 13

Advertising
background image

Ethernet-to-DeviceNet Linking Device 13

Rockwell Automation Publication 1788-IN055C-EN-P - September 2011

The switch represents the binary value of the last byte in the 4-byte IP address. In
this case it is

n. If n = 0, the linking device obtains its IP address from the

software configuration (DHCP or web page).

Setting the IP Address By Using DHCP/BootP

When DHCP/BootP is enabled and a DHCP or BootP server is found, the
IP address, Subnet mask, and Gateway address are automatically configured
by the DHCP server, as shown in the following figure.

Automatic Configuration

Follow these steps to change the IP address, Subnet mask, and Gateway address
from this dialog box.

IP address

192.168.1.n

Subnet mask

255.255.255.0

Gateway address

0.0.0.0 (No gateway set)

TIP

The use of DHCP is the default configuration for the linking device as shipped.
The IP address configuration DIP switch ships with n =0.

Advertising