36 Ethernet-to-DeviceNet Linking Device

Rockwell Automation Publication 1788-IN055C-EN-P - September 2011

Assembly Objects and Connections

Three Assembly Object instances are accessible from EtherNet/IP: input,
output and status. The input and output assemblies are linked to the input and
output tags created in RSLogix 5000 software. The status assembly provides
current status information about the linking device.

The assembly instances associated with these three assemblies are listed in the
following tables.

Input Assembly

The input assembly contains a 32-bit status register followed by the data in the
linking device’s input data table.

The input data format and content is determined by the DeviceNet scanner
configuration. The data appears in the table as it is mapped from the DeviceNet
input connections. The input data in the assembly is 124 DINTs long; however,
only the size of the input data table will be used. The remaining space will be
filled with the value 0 (zero).

IMPORTANT

With a specific 1788-EN2DN profile, I/O tags are mapped without an offset.
For example, RSLogix 5000 version13 input tag EN2DN:I:Data[0] corresponds
to word 0 of the RSNetWorx for DeviceNet software input mapping table.

Input Assembly Format

DINT
Offset

Size in

DINTs

Description

RSLogix 5000 software
version 12 example tags

RSLogix 5000 software
version 13 or later
example tags

0

1

Status register

EN2DN:

I.Data[0]

EN2DN:

I.Status Register

1

Up to
123

Input data

EN2DN:

I.Data[1 - 124]

EN2DN:

I.Data[0 …123]