Rockwell Automation 1788-EN2DN Ethernet-to-DeviceNet Linking Device User Manual

Page 38

Advertising
background image

38 Ethernet-to-DeviceNet Linking Device

Rockwell Automation Publication 1788-IN055C-EN-P - September 2011

Status Assembly Format

Byte
Offset

Size in
Bytes

Data
Type

Name (RSLogix 5000
software version 13
or later)

Description

0

4

UDINT

Scan Counter

The number of DeviceNet I/O scans
that have taken place since power
was applied to the linking device.

4

8

64-bit
Bitstring

Device Failure Register

Indicates which DeviceNet slaves are
faulted. Each bit represents the status
of the slave at the corresponding MAC
ID.

12

8

64-bit
Bitstring

Auto Verify Failure
Register

Indicates which DeviceNet slaves are
the incorrect device type. Each bit
represents the status of the slave at
the corresponding MAC ID.

20

8

64-bit
Bitstring

Device Idle Register

Indicates which DeviceNet slaves are
in Idle mode. Each bit represents the
status of the slave at the
corresponding MAC ID.

28

8

64-bit
Bitstring

Active Node Register

Indicates which DeviceNet nodes are
configured in the 1788-EN2DN’s scan
list. Each bit represents the status of
the slave at the corresponding MAC
ID.

36

4

ASCII[4]

Status Display

Mimics a 4-character alpha-numeric
display. If there are no faults, the
display shows the linking device’s
MAC ID and its Run/Idle status.
If there are faults, the display will
scroll through the MAC IDs of the
faulted nodes and display the error
code associated with each.

40

1

USINT

Scanner Address

The DeviceNet MAC ID of the linking
device.

41

1

USINT

Scanner Status

The current status of the DeviceNet
scanner.