48 Ethernet-to-DeviceNet Linking Device

Rockwell Automation Publication 1788-IN055C-EN-P - September 2011

88

The connection choices (such as polled or
strobed) between the primary connection
and the shared input only connection do not
match

Reconfigure the shared input
only connection's choices to be
the same as, or a subset of, the
primary connection's choice(s).

89

Slave device initialization using Auto Device
Replacement parameters failed

Put the slave device into
configurable mode.
Check the slave's EDS file, if the
slave is configured offline.
Check to see if the slave device
has been replaced with an
incompatible device.

90

User has disabled communication port

Check Module Command Register
for DISABLE bit set.

91

Bus-off condition detected on comm port.
Module is detecting communication errors

Check DeviceNet connections and
physical media integrity. Check
system for failed slave devices or
other possible sources of network
interference.

92

No network power detected on
communication port

Provide network power. Make
sure that module drop cable is
providing network power to
module comm port.

95

Application nonvolatile memory update in
progress

Do nothing. Do not disconnect
the module while application
nonvolatile memory update is in
progress. You will lose any
existing data in the module’s
memory.

96

COMM port in Test mode

Do nothing.

97

Module operation halted by user command

Check Module Command Register
for HALT bit set.

98

General firmware error

Replace module.

99

System failure

Replace module.

Node Status Codes (cont.)

This status code

Means

So you should