Rockwell Automation Publication 1788-IN055C-EN-P - September 2011

Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration
IEC 60068-2-6 (Test Fc, Operating)

5 g @ 10…500 Hz

Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

ESD immunity
IEC 61000-4-2

6 kV contact discharges
8 kV air discharges

Radiated RF immunity
IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
1890 MHz
1V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz

EFT/B immunity
IEC 61000-4-4

±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports

Surge transient immunity
IEC 61000-4-5

±1 kV line-line(DM) and ±2 kV
line-earth(CM) on power ports
±2 kV line-earth(CM) on communication
ports

Conducted RF immunity
IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz