Rockwell Automation 1788-EN2DN Ethernet-to-DeviceNet Linking Device User Manual

Page 47

Advertising
background image

Ethernet-to-DeviceNet Linking Device 47

Rockwell Automation Publication 1788-IN055C-EN-P - September 2011

77

Data size expected by the device does not
match scan list entry

Reconfigure your module for the
correct transmit and receive data
sizes.

78

Slave device in scan list table does not exist

Add the device to the network, or
delete the scan list entry for that
device.

79

Module has failed to transmit a message

Make sure that your module is
connected to a valid network.
Check for disconnected cables.

80

Module is in IDLE mode

Put controller in RUN mode.
Enable RUN bit in module
command register.

81

Module is in FAULT mode

Check Module Command Register
for fault bit set.

82

Error detected in sequence of fragmented I/O
messages from device

Check scan list table entry for
slave device to make sure that
input and output data lengths are
correct. Check slave device
configuration.

83

Slave device is returning error responses when
module attempts to communicate with it

Check accuracy of scan list table
entry. Check slave device
configuration. Slave device may
be in another master’s scan list.
Reboot slave device.

84

Module is initializing the DeviceNet network

None. This code clears itself once
module attempts to initialize all
slave devices on the network.

85

Data size was incorrect for this device at
runtime

Slave device is transmitting
incorrect length data. Try
replacing the device.

86

Device is producing zero length data (idle
state) while module is in Run mode

Check device configuration and
slave node status.

87

The primary owner has not allocated the slave

Put the primary owner on line.

Node Status Codes (cont.)

This status code

Means

So you should