42 Ethernet-to-DeviceNet Linking Device

Rockwell Automation Publication 1788-IN055C-EN-P - September 2011

DeviceNet Network Status Indicator

I/O Status Indicator States

Indicator

Status

Description

Flashing green

Idle

Module is in Idle mode.

Solid green

Running

Module is in Run mode.

Solid orange

Hardware Initialization

The status indicator will be in this state immediately
after power is applied.

Flashing red/green

Error

A fault has been detected.

Off

No I/O

No DeviceNet I/O configured.

DeviceNet Network Status Indicator States

Indicator

Status

Description

Solid green

Online and
communicating

The linking device is on the DeviceNet network and
communicating with at least one device.

Flashing green

Online, no
communication

The linking device is on the DeviceNet network and
is not currently communicating with any devices.

Solid red

DeviceNet interface
fault

A major fault in the DeviceNet interface has been
detected. Possible causes include Bus-off or
duplicate MAC ID.

Flashing red

Connection time-out

A connection with at least one slave device has
timed out.