26 Ethernet-to-DeviceNet Linking Device

Rockwell Automation Publication 1788-IN055C-EN-P - September 2011

You should see a message in the Data received from device field
indicating that the execution was completed.

6.

Click Close.

IMPORTANT

Changes to the autobaud option configuration do not take effect until you
cycle power to the linking device. You may also have to cycle power to the
slave devices.

If the linking device is the only master on the DeviceNet network, do not
enable autobaud. Automatic communication detection requires traffic on the
network. There is typically no traffic until the master establishes connections.