BaseStation 3200 Advanced Irrigation Controller Manual

Short circuit

Wire connection between the valve biCoder and the valve solenoid is

shorted together – repair wire connections.

Valve solenoid is broken – replace solenoid.

No response

Two-wire connection to the valve biCoder is broken – repair wire and

connections to the valve biCoder.

Two-wire voltage loss is too high – check other devices in same vicinity

for high two-wire voltage loss – repair high resistance connections

between controller and devices.

Valve biCoder is damaged – remove biCoder and move it directly to the

controller to test its ability to communicate.

Possible Statuses for Soil Moisture Sensors (biSensors)

Refer to the following table for possible self-test statuses along with causes and suggestions for

resolving the issues.

Self-test

Status

Cause/Action

No response

Two-wire connection to the biSensor is broken – repair the wire and

connections to the biSensor.

Two-wire voltage loss is too high – check other devices in same vicinity

for high two-wire voltage loss – repair high resistance connections

between the controller and devices.

The biSensor is damaged – remove the biSensor and connect it directly

to the controller to test its ability to communicate.

Zero Reading •

The biSensor detection blade is damaged – if the soil temperature

reading is valid, replace the biSensor.

If the following conditions occur in the area where the biSensor is buried, you might get unusual or

inaccurate readings from the biSensor. Review these conditions along with causes and suggestions

for resolving the issues.

Condition

Causes/Action

Ground is too

dry with low

biSensor

moisture

reading

Not enough zone water time – increase water time to apply at least

½ inch of water

biSensor not being watered by its primary zone – change the assignment

or move the biSensor to the correct location

Program start times are too infrequent – increase the program start

time frequency

biSensor limit is too low – raise limit or run a biSensor calibration cycle

(refer to page 55)