Lower limit, O understanding lower & upper, Limit watering strategies o – Baseline Systems BaseStation 3200 V12 User Manual

Page 62: E 56, O understanding lower & upper limit watering, Strategies o

Advertising
background image

BaseStation 3200 Advanced Irrigation Controller Manual

7. Press the Next button to move to the Calibration Cycle field.

Never – No calibration cycle will be performed

One Time – A single calibration cycle will be performed at the next start time

Monthly – A calibration cycle will be performed each month at the first start time

Note: Calibration cycles require that soak cycles be enabled. When you set these watering

strategies, soak cycles will be automatically enabled. You may change the settings to meet

your specific needs, but if you disable the soak cycles, the calibration cycle will fail.

8. When you have finished making changes, turn the dial to the RUN position.

Note: If for any reason the biSensor becomes damaged or fails (12 hours of failed data or

communication) the corresponding primary zone and linked zones will water based on a

timed operating mode which is based on set water times and program schedule.

Understanding Lower & Upper Limit Watering Strategies

Lower Limit

This water strategy provides an excellent way to achieve healthy, deep-rooted grass. You can either

set the lower limit manually or you can have the controller perform a calibration cycle in order to

calculate the limit. Set the lower limit at the maximum allowable depletion moisture level, just

before the lawn begins to stress or wilt.

When you choose the Lower water strategy, you must set and then manage the lower watering

limit. This water strategy works well when you are not constrained by specific water days. Schedule

the program to water every day, and then let the biSensor determine which days to skip by

monitoring the moisture level. The controller only waters when the moisture level has dropped

below the lower limit, and then a full water cycle runs.

The best way to set the lower limit is to have the controller do an initial calibration cycle. Set the

Calibrate field to One Time. The calibration cycle will run during the first normally scheduled water

time that is at least two days after the biSensor installation. The system sets an initial lower limit

based on the calibration.

You have the option to adjust the auto limit by entering a value in the Limit Adjustment field. This

adjustment is added to the limit to make the soil a little wetter or a little drier than the controller

set limit.

Lower Limit Programming Requirements

Set zone water times to apply ½ - ¾ inch of water

Set program to start every day of the week as allowed by local watering restrictions (the

biSensor will block watering until it is needed)

Enable soak-cycles

Use the default lower limit water strategy to begin with

Page 56