Baseline Systems BaseStation 3200 V12 User Manual

Page 107

Advertising
background image

BaseStation 3200 Advanced Irrigation Controller Manual

Ground is too

dry with high

biSensor

moisture

reading

biSensor not being watered by its primary zone – change the assignment

or move the biSensor to the correct location

biSensor is buried too deep – rebury the biSensor to be only 3 inches

deep

Ground is too

wet with high

biSensor

moisture

reading

biSensor is buried in low area where water collects – move biSensor

from low area

biSensor not being watered by its primary zone – change the assignment

or move the biSensor to the correct location

Program start times are too often – increase the interval between start

times

biSensor limit is too high – lower limit or run a biSensor calibration cycle

(refer to page 55)

Ground is too

wet with low

biSensor

moisture

reading

biSensor not being watered by its primary zone – change the assignment

or move the biSensor to the correct location

biSensor is buried too deep – rebury the biSensor to be only 3 inches

deep

Not enough zone water time – increase water time to apply at least ½

inch of water

Checking and Repairing Two-wire Device Assignments and

Addresses

This process searches for and verifies communication with each of the devices on the two-wire.

Note: Baseline recommends that you back up your controller data before you run this process.

Refer to Backing Up Your System on page 82.

The Verify and Repair ALL process does not check the valve current or biSensor readings, and it

does not repair any faulty wiring or electrical connections. However, if it finds discrepancies in

assignments or addressing between the controller and the devices, it will attempt to repair those

discrepancies in the following order:

Repair valve biCoder to zone number

assignments

Repair biSensor addressing

Repair pause device addressing

Repair air temperature sensor addressing

Page 101

Advertising