Programming wm5 96 – Carlo Gavazzi WM5-96 User Manual

Page 18

Advertising
background image

**********MMEETTEERRSS MMEENNUU**********

TARIFF

ENERGY RESET
TOTALIZER RESET

Meters Menu

16

WM5-96 Instruction Manual

Programming WM5 96

This menu allows the user to select/set all the parameters of the ener-
gy meters. From the main menu, select METERS by means of the “

” keys and confirm with the “S” key to enter the METERS menu.

Then choose by means of the “

” keys if entering the program-

ming of the TARIFF

(2)

or entering the “ENERGY RESET” menu to

reset the meters

(16)

; confirm the selection with S”.

TARIFF

(3)

: the instrument identifies two operating modes.

BY DIG. INPUTS (by digital inputs)

(3)

: the instrument manages the

tariff changes by means of the status changes of the digital inputs pro-
grammed as TARIFF (see the section dedicated to the digital inputs).
Select BY DIG. INPUTS by means of the “

” keys and confirm

with the “S” key.

BY CLOCK

(3)

: the instrument manages the tariffs by means of the

clock integrated in the RS232 serial module. Select BY CLOCK by
means of the “

” keys and confirm with the “S” key, then set the

following additional parameters:

WEEK TYPE

(4)

: set the WEEK TYPE where for each day you can

select if it’s to be considered a working day or a holiday. The setting
of the week type is very useful to simplify the following programming
of the periods.
Select WEEK TYPE with the “

” keys and confirm with the “S”

key: you enter the window with the list of days

(5)

, select the desired

day with the “

” keys and confirm with the “S” key, then choose

by means of the “

” keys if the day is to be considered as a (W)

WORKING day or as a (H) HOLIDAY

(6)

, and confirm with the “S” key.

Proceed as above described with the remaining days. To conclude the
operation and go back to step number

(4)

, press the “S” for at least 2

seconds.

Warning: for the management of the tariffs with the “BY CLOCK”
option, when counting the energy with WM5, the AR1039 (RS232 +
RTC) option is to be installed. The tariff management “BY CLOCK” is
however possible also without this module, but in this case the
“CLOCK” function, instead of the “METERS” function is to be select-
ed, and then the subfunction “WITHOUT BACKUP”: in this case,
remember that if, for any reason, the instrument is switched off, the
current DATE and TIME will not be stored. These data will have to be
set again every time the instrument is switched on.

********** MMAAIINN MMEENNUU **********

RREEVV.. 11..44..22..66 ((AAVV55))

VT-PT RATIO
DMD/AVG CALCUL.
INSTALLED POWER

METERS

**********MMEETTEERRSS MMEENNUU**********

1

2

3

> 2s

> 2s

Measure

> 2s

BY CLOCK

BY DIG. INPUTS

Go Back

Go Back

Confirm

TTIIMMEE PPEERRIIOODD SSEELLEECCTTIIOONN

WEEK TYPE

PERIODS
DEFAULT TARIFF

TTIIMMEE PPEERRIIOODD SSEELLEECCTTIIOONN

SETTIMANA TIPO

PERIODI
TARIFFA DEFAULT

MONDAY

(W)

TUESDAY

(W)

WEDNESDAY

(W)

THURSDAY

(W)

TTIIMMEE PPEERRIIOODD SSEELLEECCTTIIOONN

SETTIMANA TIPO

PERIODI
TARIFFA DEFAULT

LUNEDI

(W)

MARTEDI

(W)

MERCOLEDI

(W)

THURSDAY

(W)

(W) WORKING

(H) HOLIDAY

> 2s

Go Back

> 2s

Go Back

> 2s

Go Back

4

5

6

TARIFF

ENERGY RESET
TOTALIZER RESET