Technical specifications – Carlo Gavazzi WM5-96 User Manual

Page 47

Advertising
background image

45

WM5-96 Instruction Manual

Reset

By means of the key-pad or
of the configuration software,
it is possible to reset the
following data:
- all the min, max, dmd,

dmd-max values.

- total and partial counters.
- latch alarms.
- all the events.

Data stamping

Type of data

Alarm, min, max, digital
input status, digital output
status as remote control,
resets. All events are stored
with date (dd:MM:yy) and
hour (hh:mm:ss) reference

Number of events

Up to 10.000

Data management type

FIFO

Data storage type

Data flash

Displaying

4 variables per page
1 page that can be laid out
by the user
Up to 36 pages

Energy meters

Up to 28 pages depending
on the selected tariff mode.
Displaying of the consumed
energy of the previous 12
months.

Stored events

10,000 events.

Display language

Selectable:
English, Italian, French,
German, Spanish

Password

Numeric code of max 4
digits from 0 to 1000;
2 protection levels of
the programming data

1st level

Password “0”: no protection

2nd level

Password from 1 to 1000:
all data are protected.

System selection

System 1

1-phase (2 wires)

System 2, unbalanced

2-phase (3 wires)

System 3, balanced

3-phase (3 wires+1CT)

System 3, unbalanced

3-phase (3 wires)
3-phase (4 wires)

Transformer ratio

CT up to 60 kA (6000 max)
VT (PT) up to 600 kV
(6000 max)

Filters

Filter operating range

0.1 to 100% of the input
electrical scale.

Filtering coefficient

1 to 255

Filter action

Display, alarms, serial outputs
(fundamental variables:
V, A, W and their derived ones).

Alarms

Working mode

“OR” or “AND” or
“OR+AND” functions (see
“Alarm parameter and
logic” page).
Freely programmable on up
to 16 alarms. The alarms
can be connected to any
variables available in the
table “List of the variables
that can be connected to”

Software functions

Wm5Soft

Multi-language software
(Italian, English, French,
German, Spanish) for
variable reading,
instrument calibration and
parameters programming.
The program runs under
Windows XP/Vista
Working mode
Three different working
modes can be selected:

- management of local

RS232 (MODBUS);
- management of local
optical port (MODBUS);
- management of a local
RS485 network (MODBUS);

Data Storing

In pre-formatted XLS files
(Excel data base).

Data Transfer

Manual or automatic at
programmable timings.

Wm5Soft parameter programming and variable reading software

Technical Specifications