44

WM5-96 Instruction Manual

Technical specifications

Output specifications

Analogue outputs (on request)

Number of outputs

Fino a 8 (max 4 x 20mA + 4
x 10VDC o 4 x 20mA o 8 x
10VDC o 8 x ±5mA)

Accuracy (@ 25°C ±5°C, R.H.

≤60%) ±0.1%FS (20mA o 10VCC)

±0.3%FS (±5mA), FS=10mA

Range

0 ÷ 20mA o 0 ÷ 10 VCC o
±5mA

Scaling factor:

Programmable within the
whole range of retransmis-
sion; it allows the retrans-
mission management of all
values from: 0 and 20 mA, 0
and 10VDC, or -5mA and
+5mA

Response time

400 ms typical
(filter excluded)

Ripple

≤ 1% (according to

IEC 60688-1, EN 60688-1)

Total temperature drift

≤ 500 ppm/°C

Load :

20 mADC

≤ 350 Ω

10 VDC

≥ 10kΩ

±5 mA

≤ 1400Ω

Insulation

see “insulation between
inputs and outputs” table

Optical communication port

According to ANSI C12.18

RS422/RS485 port (on request)

Multidrop
bidirectional (static and
dynamic variables)

Connections

2 or 4 wires, max. distance
1000m, termination directly
on the module .
Addresses:
from 1 to 247, selectable
by key-pad.

Protocol

MODBUS RTU /JBUS,

Data (bidirectional)

Dynamic (reading only)

All display variables (see
also the table “List of the
variables that can be con-
nected to”...)

Static (writing only)

All configuration parameters,
reset of energy, activation of
digital output

Stored energy

(EEPROM) max. 999.999.999
kWh/kvarh

Data format

1-start bit, 8-data bit, no
parity/even parity,
odd parity, 1 stop bit

Baud rate

9.6k, 19.2k, 38.4k, 115.2k bit/s
selectable bauds

Insulation

see “Insulation between
inputs and outputs” table

RS232 port (on request)

Bidirectional (static and
dynamic variables)

Connections

3 wires, max. distance 15m,

Data format

1-start bit, 8-data bit, no
parity, even parity,
odd parity, 1 stop bit

Baud-rate

9.6k bit/s

Protocol

MODBUS RTU /JBUS

Other data

as for RS422/485

Ethernet/Internet port

Protocols

Modbus TCP

IP configuration

Static IP

TCP port

Selectable (default 502)

Client connections

Max 5 simultaneously

Connections

RJ45 10/100 BaseTX

Digital outputs (on request)

Pulse type

Number of outputs

Up to 16

Type

Programmable from 0.001 to
1000 pulses per kWh/kvarh
(total and partial)
Outputs connectable to the
total and/or partial energy
meters (Wh/varh)

Pulse duration

100ms, < 120msec (ON),
100ms (OFF)
according to EN62053-31

Alarm type

Number of outputs

up to 16, independent

Alarm modes

Up alarm, down alarm, in
window alarm, out window
alarm. All of them can be
used with start up deactiva-
tion function and/or latch.
All the alarms can be con-
nected to all variables (see
the table “List of the vari-
ables that can be connect-
ed to”).

Set-point adjustment

from 0 to 100% of the
electrical scale

Hysteresis

from 0 to full scale

On-time delay

0 to 255s

Output status

Selectable; normally
de-energised and normally
energised

Min. response time

≤200ms, filters excluded,
Set-point on-time delay: “0 s”

Note

The 16 digital outputs
can also work as
combination of pulse
outputs and alarm
outputs.

Static (digital) outputs

(on request)

Purpose

For pulse outputs or for
alarm outputs

Signal

V

ON

1.2 VDC/ max. 100 mA

V

OFF

30 VDC max.

Insulation

see “Insulation

between inputs and out-
puts” table

Relay (digital) outputs

(on request)

Purpose

For alarm outputs or for pulse
outputs

Output type

Relay SPDT
AC 1-8A, 250VAC
DC 12-5A, 24VDC
AC 15-2.5A, 250VAC
DC 13-2.5A, 24VDC

Insulation

see “Insulation between
inputs and outputs” table

Electrical life

≥10

5

operations (@ 8A,

250V, PF1)

Mechanical life

≥30x10

6

operations

Advertising