Programming wm5 96 – Carlo Gavazzi WM5-96 User Manual

Page 31

Advertising
background image

29

WM5-96 Instruction Manual

Programming WM5 96

This submenu allows the programming of the analog outputs (0-20mA,
0-10V, -5/+5mA). Select the function ANALOG OUTPUTS

(1)

by means

of the “

” and confirm with “S”. Then select the output to be pro-

grammed by means of the “

” keys

(2)

and confirm with “S”;

afterwards set the following parameters:
VARIABLE

(3)

: select the variable to be retransmitted by means of the

analog output. Choose the function “VARIABLE”

(3)

by means of the

” keys and confirm pressing the “S” key. Then select by the “

” keys the variable to be retransmitted (the list of the variables

depends on the selected system)

(3a)

then confirm with “S”.

MIN OUT

(3)

: set the value expressed as % of the output range (0-

20mA, 0-10V, -5/+5mA) to be coupled to the minimum measured
value. The instrument displays also the maximum and minimum value
which can be set (min, max). Select the function “MIN OUT” by means
of the “

” keys and confirm with “S”. Then set the value

(3b)

by

means of the “

” keys and confirm with “S”. MAX OUT

(3)

: select

the value expressed as % of the output range (0-20mA, 0-10V, -
5/+5mA) to be coupled to the maximum measured value. The also
instrument displays the maximum and minimum value which can be
set (min, max). Select the MAX OUT function by means of the “

keys and confirm with “S”. Afterwards set the value (3c) by means of the

” keys and confirm with “S”.

MIN IN

(4)

: minimum value of the variable input range to which the

“MIN OUT” value, retransmitted by the analog output, will be coupled.
The instrument also displays the maximum and minimum value which
can be set (min, max) . Choose the function “MIN IN” by means of the

” keys and confirm with “S”. Then set the value

(4a)

by means

of the “

” keys, then confirm with “S”.

MAX IN

(4)

: maximum value of the variable input range to which the

“MAX OUT” value, retransmitted by the analog output, will be coupled.
The instrument also displays the maximum and minimum value which
can be set (min, max). Choose the MIN IN function by means of the

” and confirm with “S”. Then set the value

(4b)

by means of the

” keys and confirm with “S”.

Proceed, if possible, with the configuration of the other analog outputs
(up to a maximum of 8 outputs). To exit the menu “analog outputs”,
keep the “S” key pressed for at least 2 seconds.

Analog outputs

The instrument can manage the fol-
lowing analog outputs combinations:
Max n. 8 0-10VDC outputs; Max n.8

5/+5mADC outputs. Any combination of the
two above mentioned types considering that
each module manages up to 2 outputs. Max
n.4 0/20mADC outputs. Max n.4 0/20mADC
outputs + max n.4 0-10VDC outputs.

************MMAAIINN MMEENNUU************

RREEVV.. 11..44..22..66 ((AAVV55))

DIGITAL OUTPUTS
ALARMS
EVENTS SELEC.

ANALOG OUTPUTS

****AANNAALLOOGG OOUUTTPPUUTT MMEENNUU**

OOUUTT AA00

VVAARRIIAABBLLEE:: VV11

VARIABLE

MIN OUT
MAX OUT

1

3

> 2s

a

****AANNAALLOOGG OOUUTTPPUUTT MMEENNUU**

OUT

A0

OUT

A1

OUT

B0

OUT B1
OUT

C0

V1

A1
W1
var1

****AANNAALLOOGG OOUUTTPPUUTT MMEENNUU**

OOUUTT AA00

MMAAXX IINN:: 00..000000

MAX OUT
MIN IN

MAX IN

4

a

MAX IN ?

0

.000

0.

min

-9999G

max

9999G

MIN IN ?

0

.000

0.

min

-9999G

max

9999G

2

3a

3c

3b

4b

4a

Measure

MIN OUT ?

0

.000

0.

min

-9999G

max

9999G

MAX OUT ?

0

.000

0.

min

-9999G

max

9999G