Technical specifications – Carlo Gavazzi WM5-96 User Manual

Page 51

Advertising
background image

49

WM5-96 Instruction Manual

Used calculation formulas

Accuracy

kWh, accuracy (RDG) depending on the current

Error

10A (Imax)

10A (Imax)

5A (In)

5A (In)

0.25A
(0.05In)
0.5A
(0.1In)

0.05A

(0.01In)

0.1A

(0.02In)

+1.0%

Class 0.5 accuracy limits (active energy) EN62053-21
5(10A) start-up current: 5mA.

kvarh, accuracy (RDG) depending on the current

Error

Class 2 accuracy limits (reactive energy) EN62053-23
5(10A) start-up current: 5mA.

PF=1

PF=L0.5

or C0.8

10A (Imax)

10A (Imax)

5A (In)

5A (In)

0.25A
(0.05In)
0.5A
(0.1In)

0.1A

(0.02In)

0.25A

(0.05In)

sin

ϕ=1

sin

ϕ=0.5

+0.5%

PF=1

PF=L0.5

or C0.8

+2.5%
+2%

-1.0%

-0.5%

-2.5%

-2%

Class 0.5

Class 2

+1%

-1%

sin

ϕ=1

Technical Specifications

System variables
Equivalent three-phase voltage

Voltage asymmetry

Three-phase reactive power

Neutral current

Three-phase active power

Three-phase apparent power

Phase variables

Instantaneous effective voltage

Instantaneous active power

Instantaneous power factor

Instantaneous effective current

Instantaneous apparent power

Instantaneous reactive power

Energy metering

Where:

i= considered phase (L1, L2 or L3)
P= active power; Q= reactive power;
t

1

, t

2

=starting and ending time points

of consumption recording; n= time
unit;

t= time interval between two

successive power measurements;
n

1

, n

2

= starting and ending discrete

time points of power recording

An = A

L1

+A

L2

+A

L3

å

-

=

L L

L L

L L

L L

V

V

V

A S Y

)

(

m in

m ax

Three-phase power factor

(TPF)

å

-

=

LN

LN

LN

LN

V

V

V

ASY

)

(

min

max