Technical specifications – Carlo Gavazzi WM5-96 User Manual

Page 48

Advertising
background image

46

WM5-96 Instruction Manual

Technical specifications

Analysis principle

FFT

Harmonic measurement

Current

Up to the 63

rd

harmonic

Voltage

Up to the 63

rd

harmonic

Type of harmonics

THD (V

L

1 and V

L

1-

N

)

THD odd (V

L

1 and V

L

1-

N

)

THD even (V

L

1 and V

L

1-

N

)

The same for the other phases:
L2, L3.
THD (A

L

1)

THD odd (A

L

1)

THD even (A

L

1)

The same for the other phases:
L2, L3.

Harmonic phase angle

The instrument measures the
angle between the single har-
monic of “V” and the single
harmonic of “I” of the same
order. According to the value
of the electrical angle, it is
possible to know if the distor-
tion is absorbed or generated.

Note: if the system has 3
wires the angle cannot be
measured.

Harmonic details

The harmonic contents is dis-
played as a graph showing
the whole harmonic spec-
trum. This value is also given
as a numerical information:
THD % / RMS value
THD even % / RMS value
THD odd% / RMS value
single harmonics in % /
RMS value

System

The harmonic distortion
can be measured in single-
phase, 3-wire or 4-wire
systems.
Tw: 0.02 sec@50Hz with-
out filter

Harmonic distortion analysis

Meters

Total

4 (9-digit)

Partial and multitariff

48 (9-digit)

Tariffs

Up to 12

Time periods

Number of periods

Up to 24 per day
Up to 100 different days per
year

Pulse output

Connectable to total and/or
partial meters (multitariff)

Energy meter recording

Consumption history by
recording of the monthly
energy meters (12 previous
months). Recording of
total and partial energy
meters.
Energy meter recording
(EEPROM)
Max.999.999.999kWh/kvarh.

Time period management

Energy Meters

Total energy meters

4 (+kWh, +kvarh, -kWh, -kvarh)
It is possible to divide each
energy meter here above listed
in 3 additional energy meters
(1 for each phase “L1-L2-L3”)

Monthly energy meters

48 (energy meters for
each month: “+kWh, +kvarh,
-kWh, -kvarh”)

Partial energy meters

16 (using digital inputs:
max 4 tariffs).
48 (using the internal clock:
max 12 tariffs)

Advertising