Technical specifications – Carlo Gavazzi WM5-96 User Manual

Page 45

Advertising
background image

43

Number of analogue inputs

Current

1 (1-phase; system code: 3)
3 (3-phase; system code: 3)

Voltage

1 (1-phase; system code: 3)
4 (3-phase; system code: 3)

Digital inputs (on request)

Up to 12

AQ1038

No. of inputs: 3 (voltage-free)

Purpose

“dmd” measurements
synchronisation.
Tariff selection: energy.
Contact status reading.
Clock synchronisation.

Contact measuring current

<8mA/ 17.5 to 25VDC

AQ1042

Number of inputs: 3 +
excitation output

Purpose

“dmd” measurements
synchronisation.
Tariff selection: energy.
Contact status reading.
Clock synchronisation.

Excitation output

16V<+Aux<24VDC Max15mA

Contact measuring current

15mA

Common characteristics

Close contact resistance

Max 1k

Open contact resistance

Min 100k

Insulation

see “Insulation between
inputs and outputs” table

Accuracy

(display, RS232, RS485)
In: 5A, If.s.: 10A
Un: see voltage ranges below

Current (A

L1

, A

L2

, A

L3

)

from 0.05In to Imax:
(@20°C ±5°C, R.H.

≤75%)

±(0.2%RDG+2DGT)
from 0.01In to 0.05In:
±(0.5%RDG+2DGT)

Current (A

n

)

±0.5% RDG (0.2 to 2 In)
from 40 to 100 Hz

Voltage

(@20°C±5°C, R.H.

≤75%)

range AV5:

400/690V

L-L

AC

V

L-N

: from 185 V to 460 V

V

L-L

: from 320 V to 800 V

±(0.2%RDG+1DGT)

range AV6:

120/208V

L-L

AC

V

L-N

: from 45 V to 145 V

V

L-L

: from 78 V to 250 V

±(0.2%RDG+1DGT)
Includes also: frequency,
power supply and output
load influences.

Frequency

±0.1% RDG (40 to 440 Hz)

Active power and

0.05In to Imax, PF 1:

apparent power

±(0.5%RDG+1DGT)

(@ 20°C ± 5°C, R.H.

≤ 75%) 0.01In to 0.05In, PF 1:

±(1%RDG+1DGT)
0.1In to Imax, PF 0.5L,
PF 0.8C:
±(0.6%RDG+1DGT)
0.02In to 0.1In, PF 0.5L,
PF 0.8C: ±(1%RDG+1DGT)

Reactive power

(@ 20°C ± 5°C, R.H.

≤ 75%) 0.1In to Imax, senϕ 0.5L/C:

±(2%RDG+1DGT)
0.05In ÷ 0.1In, sen

ϕ 0.5L/C:

±(2.5%RDG+1DGT)
0.05In ÷ Imax, sen

ϕ 1:

±(2%RDG+1DGT) 0.02In to
0.05In, sen

ϕ 1:

±(2.5%RDG+1DGT)

Energies

(@ 20°C ± 5°C, R.H.

≤ 75%) Active: class 0.5 according

to EN62053-22, ANSI C12.20
Reactive: class 2 according
to EN62053-23, ANSI C12.1
In: 5A, Imax: 10A
0.1In: 500mA,
Start-up current: 5mA Un:
400/690V

L-L

(AV5)

Un: 120/208V

L-L

(AV6)

Harmonic distortion

1% FS (FS: 100%)

(@ 20°C ± 5°C, R.H.

≤ 75%)

fase: ±2°; Imin: 5mA

RMS

;

Imax: 15Ap; Umin: 30V

RMS

;

Umax: 500Vp

Temperature drift

≤200ppm/°C (A/V), ≤300ppm/°C
(all other measurements)

Sampling rate

6400 samples/s @ 50Hz
7680 samples/s @ 60Hz

Display

Graph LCD, backlighted
(128x64 dots). Read-out for
instantaneous variables:
4x4 digit
Total energies: 4x9 digit;
Partial energies: 4x9 digit

Display refresh time

100ms

Max. and min. indication

Max. 9999 (999,999,999),
Min. -9999 (–999,999,999)

Front LED

Red
Blinking light in case of vir-
tual alarm. Fixed light in
case of digital output acti-
vation (alarm)

Measurements

Current, voltage, power,
energy, power factor, fre-
quency, harmonic distortion
(see “Display pages”). TRMS
measurement of a distorted
wave (voltage/current).

Coupling type

Direct

Crest factor

< 3, max 10A peak

Input impedance

400/690V

L-L

(AV5)

1.77 M

Ω ±5%

120/208V

L-L

(AV6)

885 k

Ω ±5%

Current

≤ 0.01Ω

Frequency

40 to 440 Hz

Overload (maximum values)

Permanent: voltage/current

AV5: 460V

LN

, 800V

LL

/10A

AV6: 145V

LN

, 250V

LL

/10A

For 500ms: voltage/current

AV5: 800V

LN

, 1380V

LL

/36A

AV6: 240V

LN

, 416V

LL

/36A

Input Specifications

Technical specifications

WM5-96 Instruction Manual

Advertising