Carlo Gavazzi WM5-96 User Manual

Page 23

Advertising
background image

Programming WM5 96

21

WM5-96 Instruction Manual

This function allows the operating modes selection of the digital
inputs. Choose the function DIGITAL INPUTS

(1)

by means of the “

” keys and confirm with the “S” key.

(2)

Select the digital input (ex.:

A1=digital input 1 of slot A) by means of the “

” keys, the instru-

ment displays the function of the selected input (the inputs are set on
REMOTE as default), press “S” to confirm the selected digital input.

(3)

From the list, select the operating mode to be coupled to the selected
digital input by means of the “

” keys, the functions are:

REMOTE

(3)

: the status of the digital inputs is displayed from the

instrument and retrasmitted (if requested) by the serial communication.
SYNC (SYNCHRONISM)

(3)

: synchronises the calculation of the

“dmd” power by means of an external signal.
TARIFF LSb and MSb

(3)

: This function allows the digital inputs to

control the tariffs in the energy metering. The combination of the input
status manages the tariff change as specified in the table

(18-1)

. If only

the “MSb” (one digital input only) is selected, then the energy meter-
ing is possible with a maximum of 2 tariffs: the tariff change will only
be possible between tariff 1 and tariff 3. If only the “LSb” is selected,
then the tariff change occurs only between tariff 1 and tariff 2. The use
of both digital inputs (MSb + LSb) allows the management of tariffs 1,
2, 3 and 4. Press “S” to confirm the selection. Proceed, if necessary,
with the configuration of the other digital inputs.

(18-1)

TOTALIZERS

(3)

: This function allows the digital inputs to totalize the

gas, water (hot or cold) and the remote heating. From the totalizer
menu select: TYPE

(4)

, to choose what the instrument has to totalize

(4a)

GAS, HOT H2O (hot water), COLD H2O (cold water) or REMOTE

HEAT: in this case the WM5 counts the hot water by the digital input
through an external water counter but on the display the relevant value
is reported in “kWh”.
ENG. UNIT

(4b)

, to choose the correct engeegniring unit

(4b)

to

associate to the totalizer selected before.
PULSES

(4c)

, to set the pulse weigth

(4c)

, that is for each input pulse

the totalizer increases in the chosen value.

MSb

LSb

Tariff

off

off

1

off

on

2

on

off

3

on

on

4

Digital Inputs

************MMAAIINN MMEENNUU************

RREEVV.. 11..44..22..66 ((AAVV55))

INSTALLED POWER
METERS
DISPLAY PAGE

DIGITAL INPUTS

******DDIIGGIITTAALL IINNPPUUTTSS******

RREEMMOOTTEE

IN C1

IN C2
IN C3

******DDIIGGIITTAALL IINNPPUUTTSS******

RREEMMOOTTOO

ING. C1

ING. C2
ING. C3

1

2

3

> 2s

> 2s

Measure

> 2s

Go back

Go back

REMOTE
SYNC
TARIFF LSb
TARIFF MSb

TOTALIZER

******TTOOTTAALLIIZZEERR MMEENNUU******

TYPE

ENG. UNIT
PULSES

4

m3/PULSE

10000s

min

0.001

s

max

1000

s

GAS

HOT H2O
COLD H2O

4a

4c

4b

REMOTE HEAT

m3

Gal
Lit
dm3

Lit
dm3
Ft3
kWh

> 2s

Go back

Input
pulse

Weight of pulse
selected: 10.

0

10

20

30 ...