Installation/Operation Manual - Appendix

61

10.2 Configuration Parameters for CB-2 Weighed Materials Discharged Using an

Open Close Gate

When configuring the CB-2 for an open close gate it is important to know the time in seconds required to fully

open and close the gate. Manually open the discharge gate and record the amount of time in seconds required to

fully open the gate. Repeat a few times for accuracy. Average the time readings and this number will represent

the “fully open time” for the gate. This process can be repeated to calculate the “fully closed time”.

Admin Menu

Database

Scales

Aggregate (OR) Cement

Scale Type - Hopper

Close Time

Measured time in seconds to close the gate. This number will be used if the gate does not have a limit switch.

Gate Open Time

Measured time in seconds to fully open the discharge gate.

Wide Open Weight

When the material weight left to discharge falls below this value the inching gate will open fully. This adjustment

serves as a “clean out” action. The aggregate scale will not open fully even when the material weight falls below

this value until the cement has totally discharged. In this situation, the aggregate gate will close until the cement

is discharged and then open fully.
If this number is set too high material can overflow an aggregate belt if used. This parameter is applicable for a

hopper type scale.
Inch Time = 0
Control Rate Filter = 0
Target Discharge Rate = 0
Discharge Rate Tolerance = 0
Discharge Controls
Gate Type = Open Close