Page 8

Bradford White Corp.

the enclosure shall be provided. The openings shall

communicate directly, or by ducts, with the outdoors

or spaces that freely communicate with the outdoors.

When directly communicating with the outdoors, or

when communicating to the outdoors through vertical

ducts, each opening shall have a minimum free area

of 1 square inch per 4000 Btu/hr (550 square mm/kW)

of total input rating of all equipment in the enclosure.

When communicating to the outdoors through horizontal

ducts, each opening shall have a minimum free area of

not less than 1 square inch per 2000 Btu/hr (1100 square

mm/kW) of total input rating of all equipment in the

enclosure.

Method 2: One permanent opening, commencing

within 12" (300mm) of the top of the enclosure, shall

be permitted. The opening shall directly communicate

with the outdoors or shall communicate through a

vertical or horizontal duct to the outdoors or spaces

that directly communicate with the outdoors and shall

have a minimum free area of 1 square inch per 3000

Btu/hr (734 square mm/kW) of the total input rating of

all equipment located in the enclosure. This opening

must not be less than the sum of the areas of all vent

connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform to

the requirements in the applicable codes listed above.

In Canada, consult local building and safety codes

or, in absence of such requirements, follow CAN/CGA

B149.

3.1.2 Ducted Combustion Air

The combustion air can be taken through the wall,

or through the roof. When taken from the wall, it must

be taken from out-of-doors by means of the Bradford

White horizontal wall terminal, shown in

Table 3

. See

Table 2

to select the appropriate diameter air pipe. When

taken from the roof, a field-supplied rain cap or an

elbow arrangement must be used to prevent entry of rain

water (see

Figure 7

).

Use ABS, PVC, CPVC or galvanized pipe for the

combustion air intake (see

Table 4

), sized per

Table 2

.

Route the intake to the boiler as directly as possible.

Seal all joints. Provide adequate hangers. The unit must

not support the weight of the combustion air intake pipe.

Maximum linear pipe length allowed is shown in

Table

2

. Subtract 5 allowable linear ft. (1.5m) for every elbow

used.

The connection for the intake air pipe is at the top

of the unit (see

Figure 2

).

In addition to air needed for combustion, air

SECTION 3.

Venting and Combustion Air

Bradford White Brute Elite includes a

standard CPVC vent/combustion air

adapter. If field connections require

use of PVC/CPVC vent materials, the

installer must use proper adhesive to

join CPVC and/or PVC pipe and fittings.

3.1 Combustion Air

Brute Elite boilers and water heaters must

have provisions for combustion and ventilation air

in accordance with the applicable requirements for

Combustion Air Supply and Ventilation in the National

Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural

Gas and Propane Installation Code, CSA B149.1. All

applicable provisions of local building codes must also

be adhered to.

A Brute Elite unit can take combustion air from

the space in which it is installed, or the combustion

air can be ducted directly to the unit. Ventilation air

must be provided in either case.

3.1.1 Combustion Air from Room

In the United States, the most common

requirements specify that the space shall communicate

with the outdoors in accordance with method 1 or 2,

which follow. Where ducts are used, they shall be of

the same cross-sectional area as the free area of the

openings to which they connect.

Method 1: Two permanent openings, one

commencing within 12" (300mm) of the top and one

commencing within 12" (300mm) of the bottom, of

INSTALLATION STANDARDS

MATERIAL

UNITED STATES

CANADA

ABS

ANSI/ASTM D1527

PVC, sch 40

ANSI/ASTM D1785 or D2665

Air pipe material must be chosen

CPVC, sch 40

ANSI/ASTM F441

based upon the intended application of the boiler.

Single wall galv. steel

26 gauge

Table 4. Required Combustion Air Pipe Material.

CONCENTRIC

WALL

ROOF

SIZE

ADAPTER

TERMINAL

TERMINAL

125

3CGV-VC

3CGV-AD-

3CVG-HZC

Table 3b. Approved Stainless Steel

Terminations and Adapters.

HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL

KITS

2" PVC

3" PVC

SIZE

Standard

Concentric

n/a

CA006000

125

included

optional contact Bradford White

Concentric vent terminal = 10 ft. pipe length.

Table 3a. PVC Vent Terminal Kits.