Bradford White BLMC125NA User Manual

Page 11

Advertising
background image

Page 9

The Brute Elite 125

INSTALLATION STANDARDS

MATERIAL

UNITED STATES

CANADA

Stainless Steel

UL 1738

Venting must be ULC-S636 certified for use as

PVC, sch 40

ANSI/ASTM D178

venting material. The venting material must be chosen

CPVC, sch 40

ANSI/ASTM F441

based upon the intended application of the boiler.

Table 5. Required Exhaust Vent Material.

shall also be supplied for ventilation, including air

required for comfort and proper working conditions for

personnel.

3.2 Venting (Exhaust)

WARNING

Failure to use the appropriate vent material, installation

techniques, glues/sealants could lead to vent failure

causing property damage, personal injury or death.

WARNING

All venting must be installed according to this manual

and any other applicable local codes, including but

not limited to, ANSI Z223.1/NFPA 54, CSA B149.1,

CSAB149.2 and ULC-S636. Failure to follow this manual

and applicable codes may lead to property damage,

severe injury, or death.

The flue temperature of the Brute Elite changes

dramatically with changes in operating water

temperature. Therefore, it is necessary to assess the

application of the boiler to determine the required

certified vent class. If the Brute Elite is installed in

an application where the ambient temperature is

elevated, and/or installed in a closet/alcove, CPVC

or stainless steel material is required. If the system

temperatures are unknown at the time of installation,

stainless or CPVC material is recommended.

The Brute Elite is a Category IV appliance and

may be installed with PVC and CPVC that complies

with ANSI/ASTM D1785 F441, or a stainless steel

venting system that complies with UL 1738 Standard

(see

Table 5

).

INSTALLATIONS IN CANADA require the use

of venting material certified to ULCS636. All Gas

vents connected to the Brute Elite, plastic, stainless

steel or otherwise must be certified to this ULC

standard. Appropriate selection of vent material is

very important for proper performance and safe

operation of the Brute Elite.

The flue temperature of the Brute Elite changes

dramatically with changes in operating water

temperature. Therefore, it is necessary to assess the

application of the boiler to determine the required

certified vent class. If the Brute Elite is installed in

an application where the outlet water temperature

exceeds 145°F, and/or installed in a closet, class IIB

or higher vent material is required. If the system

temperatures are unknown at the time of installation,

class IIB or higher venting material is recommended.

IN CANADA all venting used must meet the

following requirements:

1. ULC-S636 certified and marked

2. The first 3 feet of venting must be accessible for

visual inspection.

3. All components used in the vent system must be

from a certified manufacturer.

4 . Vent system components must not be mixed

with alternate manufacturers certified

components and/or unlisted components.

5 . The venting must be installed according to the

vent manufacturers installation instructions.

The unit’s vent can terminate through the roof, or

through an outside wall.

See

Table 2

to select the appropriate vent pipe

diameter. Vent pipe must pitch upward, toward the vent

terminal, not less than 1/4" per foot, so that condensate

will run back to the Brute Elite to drain. Route vent

pipe to the heater as directly as possible. Seal all

joints and provide adequate hangers as required in the

venting system manufacturer’s Installation Instructions.

Horizontal portions of the venting system must be

supported to prevent sagging and may not have any low

sections that could trap condensate. The unit must not

support the weight of the vent pipe. Please see

Table 2

for proper diameter vs. length allowed.

Figure 7. Combustion Air and Vent Through Roof.

Advertising
This manual is related to the following products: