The Brute Elite 125

SECTION 5.

Pump Capacity

5.1 Brute Elite Heating System

Pump Capacity

HEATING

DHW

SIZE

CONN SIZE

CONN SIZE

125

3/4"

1/2"

Table 7. Water Connection Pipe Sizes.

when rigid hangers are installed. Maintain 1" (2.5cm)

clearance to combustibles for hot water pipes.

Pipe the discharge of the pressure relief valve (full

size) to a drain or in a manner to prevent injury in the

event of pressure relief. If system contains more than

24 gallons (91 liters), then an auxiliary expansion tank

is required. Minimum fill pressure must be 12psig

(82.7kPa). Install shutoff valves where required by code.

Suggested piping diagrams are shown in

Figures

12 through 19

. These diagrams are meant only as a

guide. Components required by local codes must be

properly installed.

Brute Elite's efficiency is higher with lower

return water temperatures.

Brute Elite MUST be piped in a primary-secondary

fashion (using either piping or a hydraulic separator)

such that the pump that is mounted on the boiler ONLY

serves the boiler.

Brute Elite boiler must be located within 15 feet

(4.6m) of the supply and return header (or the hydraulic

separator). The pump is sized for a maximum of 30 feet

(9.1m) of piping and the headloss of the boiler only.

For custom configurations, the available pump

head is provided in

Figure 11.

The system designer

should take into account allowable boiler temperature

rise of 65°F (36°C).

6.2 Cold Water Make-Up

1. Connect the cold water supply to the inlet

connection of an automatic fill valve.

2. Install a suitable back flow preventer between the

automatic fill valve and the cold water supply.

3. Install shut off valves where required.

Figure 11. Available Pump Head.

Figure 12. DHW Connections with Anti-Scald Valve and

Flow Restrictor.

SECTION 6.

Water Connections

6.1 Central Heat System Piping

NOTE: This appliance must be installed in a closed

pressure system with a minimum of 12 psi (82.7kPa)

static pressure at the boiler.

Hot water piping should be supported by suitable

hangers or floor stands. Do not support piping with

this appliance. Due to expansion and contraction of

copper pipe, consideration should be given to the type

of hangers used. Rigid hangers may transmit noise

through the system resulting from the piping sliding in

the hangers. It is recommended that padding be used

PRV

Included with

Brute Elite

A Pressure Relief Valve

is included with each Brute

Elite. The PRV must be installed prior to filling the system.