Bradford White BLMC125NA User Manual

Page 12

Advertising
background image

Page 10

Bradford White Corp.

IMPORTANT NOTE ABOUT COMMON VENTING: A

single vent that is shared by multiple Brute Elite units

MUST be engineered by a competent venting specialist,

and involves the selection of draft inducing equipment,

hardware and controls to properly balance flue gas

pressures.

Do not common vent Brute Elite units

unless the vent system meets this requirement.

Brute Elite units are never permitted to share a vent

with Category I appliances.

3.3 Locating Vent & Combustion Air

Terminals

3.3.1 Side Wall Vent Terminal

The appropriate Bradford White side wall vent

terminal must be used. The terminal must be located in

accordance with ANSI Z223.1/NFPA 54 and applicable

local codes. In Canada, the installation must be in

accordance with CSA B149.1 or .2 and local applicable

codes. Consider the following when installing the terminal:

1.

Figure 9

shows the requirements for mechanical

vent terminal clearances for the U.S. and Canada.

2. Vent terminals for condensing appliances or

appliances with condensing vents are not permitted

to terminate above a public walkway, or over an

area where condensate or vapor could create a

nuisance or hazard.

3. Locate the vent terminal so that vent gases cannot

be drawn into air conditioning system inlets.

4. Locate the vent terminal so that vent gases cannot

enter the building through doors, windows, gravity

inlets or other openings. Whenever possible, avoid

locations under windows or near doors.

5. Locate the vent terminal so that it cannot be

blocked by snow. The installer may determine

that a vent terminal must be higher than the

minimum shown in codes, depending upon local

conditions.

6. Locate the terminal so the vent exhaust does not

settle on building surfaces or other nearby objects.

Vent products may damage surfaces or objects.

7. If the boiler or water heater uses ducted

combustion air from an intake terminal located on

the same wall, see

Figure 9

for proper spacing and

orientation.
If the vent termination is located in an area

exposed to high winds, an optional PVC tee (the same

diameter as the vent pipe) may be used. The tee'd vent

termination offers greater protection from wind related

operating issues.

3.3.2 Side Wall Combustion Air Terminal

The Bradford White side wall combustion air

terminal, or concentric terminal (

see Table 3

), must

be used when the heater takes air from a side wall.

Consider the following when installing the terminal (

see

Figure 9

):

1. Do not locate the air inlet terminal near a source

of corrosive chemical fumes (e.g., cleaning fluid,

chlorine compounds, etc.)

2. Locate the terminal so that it will not be subject

to damage by accident or vandalism. It must be at

least 7 feet (2.1m) above a public walkway.

3. Locate the combustion air terminal so that it cannot

be blocked by snow. The National Fuel Gas Code

requires that it be at least 12 inches (30cm) above

grade, but the installer may determine it should be

higher, depending upon local conditions.

4. For concentric vent, follow instructions

included with vent kit.

5. Multiple vent kits should be installed such that the

horizontal distance between outlet group and inlet

group is 36" (90cm) minimum.

6. Vent outlet must be no lower than the center of

the air inlet, and must be at least 12" (30cm) away

from the air inlet (see

Figure 8

).

3.3.3 Vertical Vent Terminal

When the unit is vented through the roof, the vent

must extend at least 3 feet (0.9m) above the point at

which it penetrates the roof. It must extend at least 2 feet

(0.6m) higher than any portion of a building within a

horizontal distance of 10 feet (3.0m), and high enough

above the roof line to prevent blockage from snow.

When the combustion air is taken from the roof, the

combustion air must terminate at least 12" (30cm) below

the vent terminal (

see Figure 7

).

3.3.4 Vertical Combustion Air Terminal

When combustion air is taken from the roof, a

field-supplied rain cap or an elbow arrangement must be

used to prevent entry of rain water (

see Figure 7

). The

opening on the end of the terminal must be at least 12"

(30cm) above the point at which it penetrates the roof,

and high enough above the roof line to prevent blockage

from snow. When the vent terminates on the roof, the

combustion air must terminate at least 12" (30cm) below

the vent terminal.

Figure 8. Minimum Venting Distance.

Advertising
This manual is related to the following products: