SECTION 2.

Locating the Appliance

2.1 Locating the Appliance

Brute Elite is for indoor, wall-mounted

installations only.

The appliance should be located to provide

clearances on all sides for maintenance and inspection.

It should not be located in an area where leakage of any

connections will result in damage to the area adjacent to

the appliance or to lower floors of the structure.

When such a location is not available, it is

recommended that a suitable drain pan, adequately

drained, be installed under the appliance.

The appliance is design certified by CSA-

International for wall-mounted installation in

basements; in closets, utility rooms or alcoves. The

location for the appliance should be chosen with regard

to the vent pipe lengths and external plumbing and

on a plumb (vertical) wall. The unit shall be installed

such that the gas ignition system components are

protected from water (dripping, spraying, rain, etc.)

during operation and service (circulator replacement,

control replacement, etc.). When vented vertically, the

Brute Elite must be located as close as practical to the

vertical section of the vent. If the vent terminal and/or

combustion air terminal terminate through a wall, and

there is potential for snow accumulation in the local

area, both terminals should be installed at an appropriate

level above grade or the maximum expected snow line.

The dimensions and requirements that are shown

in

Table 1

should be met when choosing the locations

for the appliance.

2.2 Locating Appliance for Correct Vent

Distance from Outside Wall or

Roof Termination

The forced draft combustion air blower in the

appliance has sufficient power to vent properly when the

guidelines in

Table 2

are followed.

NOTE: When located on the same wall, the Brute Elite

combustion air intake terminal must be installed a

minimum of 12" below the exhaust terminal.

For concentric vent terminal kit (optional), follow

installation instructions included with the kit.

APPLIANCE

SUGGESTED SERVICE ACCESS CLEARANCE

SURFACE

INCHES

CM

Left Side

6

15

Right Side

6

15

Top

6

15

Closet, Front

6

15

Front

24

61

Vent

1

3

Certified by CSA for zero clearance to

combustible materials on all sides.

Table 1. Clearances.

INTAKE / EXHAUST

MAX EQUIV.

CONCENTRIC MAX EQUIV.

SIZE

VENT

FT.

M

VENT

FT.

M

125

2"

40

6.1

3/5"

40

6.1

125

*

3"

*

100 30.5

3/5"

40

6.1

Installations in the U.S. require exhaust vent pipe that is a combination
of PVC & CPVC complying with ANSI/ASTM D1785 F441 or stainless
steel complying with UL1738. Installations in Canada require exhaust
vent pipe that is certified to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with ANSI/ASTM
D1785 F441, ABS that complies with ANSI/ASTM D1527 or galvanized
material.
Installer must comply fully with manufacturer's installation instructions,
to maintain ANSI Z21.13 safety certification.
Closet and alcove installations do not allow the use of PVC under any
circumstances
To calculate max equivalent length, measure the linear feet of the pipe,
and add 5 feet (1.5m) for each elbow used.
* Must use 2x3 adapter within 1 ft. (30cm) of boiler exhaust outlet.

Table 2. Vent / Air Pipe Sizes.